|
Home Order Contact Us
|
TEMPERATURE CONTROLLED BLOWER MODULATION FOR AIR
CONDITIONING HUMIDITY CONTROL.
By
Richard Peters PE, CM
The purpose of this article is to explain
some of the common problems encountered with humidity control in modern
high-speed air conditioning and how controlling blower speed from a temperature
signal can eliminate these common problems as well as increase the comfort and
livability of a home.
FACTS AND RULES OF THUMB THAT YOU CAN TAKE TO THE BANK
-
If
water stands in a drain pan, the pan is either poorly designed or
improperly installed.
-
What
is normally called “low load conditions” refers to load from temperature
gain and is not necessarily the total load necessary for efficient
operation and comfort.
-
Humidity
can be a significant load that is not addressed.
-
Every
10% drop in relative humidity is the comfort equivalent of a 3° drop in
temperature. I.e. drop the humidity by 10% and you can enjoy the same
level of comfort at a three-degree higher thermostat setting. This saves
energy.
-
Water
adheres to the A/C coil better as the coil gets colder.
-
When
the A/C compressor turns off and the blower’s speed remains high, the coil
gets warm very quickly and doesn’t grip the water as tightly.
-
The
faster that air moves over an A/C coil, the higher the coil’s bypass
factor, the warmer the coil, the warmer the delivered air temperature and
the less adhesion to water.
-
A warm
coil (either right after the compressor shuts off or under high air
velocity) doesn’t hold water tight enough to give it time to flow down the
entire height of the coil to the drain pan before being blown from the
coil by the high-speed air movement through the coil.
-
If
(with the compressor running) the air velocity over the coil is less than 500 feet per minute: An A/C coil,
under normal operating conditions, will hold water long enough for it to
flow down the coil and into the drain pan.
-
The
method of determining the air velocity (called face velocity) over the
coil is to divide the CFM air delivery from the blower by the square foot
face area of the coil. When velocities reach over 600 feet per minute,
then water will strip from the coil and down the ducts even if the coil is
quite cold.
- PHYSICAL
CONSIDERATIONS THAT REQUIRE DISCUSSION.
-
The
space between the coil plates or fins (Usually 14 fins per inch) is
designed to allow air to move freely through the coil and still allow
enough air to impact the coil to reduce the temperature of the air enough
for effective cooling.
-
The
thickness of the coil. Usually allows 3 or 4 rows of tubing.
-
Water
that is flowing down the coil takes up space. There is a condition where
the amount of water in the coil can build up because it can’t get down to
the drain pan fast enough, this excess water takes up free space and
reduces the amount of free area for air to flow at an efficient (500 ft.
per minute) velocity through the coil. It has the same effect as reducing
the size of the coil. In this case, the air velocity through the
remaining, or available, free area increases to over 600 feet per minute.
At that point water is stripped from the coil.
-
Coil bypass factor is the
percentage of air that goes through a coil without being affected by the
coil. Cooling is done only to the air that actually touches the coil’s
fins.
-
Typical
bypass factors for a three-row coil with 14 fins per inch are:
|
FACE VELOCITY IN FEET PER MINUTE
|
BYPASS FACTOR OR PERCENT OF AIR NOT
COOLED BY THE COIL
|
COMMENT
|
|
600
|
23%
|
WATER SURFACE
TENSION BROKEN RESULTING IN WATER SPRAYING DOWN THE DUCTWORK.
|
|
500
|
18%
|
500 FT PER MINUTE
IS USUAL ENGINEERING DESIGN FOR MAXIMUM FACE VELOCITY
|
|
400
|
14%
|
VERY HIGH COIL
EFFICIENCY
|
|
300
|
11%
|
|
200
|
9%
|
The delivered air temperature is the result of mixing very
cold air cooled by the coil fins and the room temperature air that goes through
the coil space without being cooled.
A COMMON ATTEMPT AT SOLVING THE HUMIDITY PROBLEM
Blower speed timed
programs: i.e. run the fan for a
number of minutes (maybe 7 minutes) on low (about ½ speed). During this time the
coil is super cold and super efficient and collects large amounts of water.
During certain high humidity conditions, the A/C coil loads up with water
faster than it will drain. After the low speed segment has timed-out, the
blower ramps to high speed. This does two things: First it warms the coil,
which reduces the water’s adhesion to the coil. Second, high velocity through
the remaining free space breaks the surface tension of the water so the
droplets break apart and they blow off the overloaded coil and down the ducts.
This is why many contractors in high humidity areas do not use this feature.
ANOTHER COMMON ATTEMPT AT SOLVING THIS PROBLEM
In high humidity areas, it is also common to either run the
fan on intermittent or turn off the fan for a period of time after the
compressor shuts down in an attempt to give the coil time to drain. This is not
a solution to the recognized problem of blowing water off the coil and
re-evaporation. It is avoiding the problem rather than solving the problem. It
also makes the home less comfortable, less quiet and the wide variety of indoor
air quality products less efficient.
DRAIN PAN PROBLEMS
The common statement concerning coil drain pans is: “When
you run the blower while the compressor is off, you’ll re-evaporate the water
standing in the drain pan.” Somehow this statement has been used to the point
that it has become folklore. The proper design and tilt of the drain pan is all
that is required for it’s proper function. First, the word drain in the name of the device should provide a clue to its
function. Water should not be standing in a drain pan. Second, to evaporate a
couple of ounces of water at temperatures we are dealing with is not
instantaneous. Third, even if a few ounces of water were evaporated into the
thousands of cubic feet of air that is inside a home, it would have about a
zero consequence.
TEMPERATURE CONTROLLED BLOWER SPEED SOLVES THE PROBLEM
MORE FACTS THAT YOU CAN TAKE TO THE BANK
-
Blower
speed can be controlled effectively and efficiently by changing the
voltage to any high quality shaded pole or PSC blower motor. It has been
done since the late 1950’s or early 1960’s.
-
When
blower speeds are controlled through quality motors, the fan laws are in
full effect.
-
When
you reduce the speed of the blower by 50%, you reduce the CFM by 50%
-
When
you reduce the speed of the blower by 50%, you reduce the static pressure
to one fourth.
-
When
you reduce the speed of the blower by 50%, you reduce the power required
to one eighth of that required to run it at full speed. (i.e. You can run
a good blower motor for eight hours at half speed for the same amount of
money that it would take to run it full speed for one hour)
-
Typical
speed/temperature relationships for blower speeds controlled by
temperature. Using a typical, average designd for a three-ton system.
(Using rounded numbers for simplicity)
-
36,000
BTUH
-
400
CFM per ton or 1,200 CFM at full speed
-
Minimum
speed is set at about 35 or 40% of full speed or about 450 CFM at about
450 rpm blower speed when the delivered air temperature coming off the
coil is above 68° F.
-
Maximum
blower speed about 1070 RPM when the delivered air temperature coming off
the coil is about 50° F.
-
The
fan is set to run continuously.
-
For
every degree of temperature reduction from 68° F delivered air the fan
motor’s speed increases about 34 RPM. Or for every 34th of a
degree temperature drop, the fan speed increases one RPM. This is smooth
and seamless.
TYPICAL AIR CONDITIONING CYCLE
USING TEMPERATURE CONTROLLED BLOWER SPEED MODULATION
-
Room
temperature about 75°.
-
Indoor
humidity high. (maybe over 70%)
-
Blower
running continuous at about 450 RPM and delivering about 450 CFM.
-
Compressor
comes on.
-
Air is
moving over the coil slowly.
-
The
bypass factor is about 10%, which means the coil is super efficient and
very cold.
-
Because
the coil is very cold and super efficient, it cuts into the latent load
and begins rapidly collecting water.
-
Because
the coil is so cold, the air coming across the coil also cools down
rapidly and reduces the delivered air temperature.
-
Because
the air temperature is reduced, the blower’s speed is automatically and
instantly increased.
- Here are some interesting points:
The coil has established its grip on the latent load and is collecting
water to the coil’s maximum design capability to capture water.
-
The
compressor doesn’t know the difference between latent and sensible loads.
It only sees a load.
- Because the coil is capturing water to it’s maximum
ability, the remaining capacity of the compressor is then devoted to the
sensible load. The remaining compressor capacity may not be enough to
drive delivered air temperature down to the 50° temperature required for
full speed blower operation. The delivered air temperature might be 54°
degrees and between 900 and 1,000 CFM. (That is why when Florida, gulf
coast and contractors in other high humidity areas first install
temperature controlled blower modulating controls, they think that the
blower is going too slow. However, when they look at their gauges, they
see the unit is working its lungs out because it is concentrating on the
latent load. A day or two later, the house has dried out. The delivered
air temperature is colder and the blower is running faster.)
- Compressor Shuts off:
- The coil and delivered air begin to warm a little. The
blower’s speed immediately and smoothly drops to about 50% of the way
between the highest speed that it achieved at its coldest point and the
450 CFM minimum speed. Lets say about 675 CFM.
- 675 CFM isn’t going to blow water off a
1,200 CFM coil. The coils is going to drain.
- Interesting point #2:
There is a good
amount of cooling capacity in pressure equalization. The high-pressure
liquid refrigerant moves into the evaporator and does some cooling. It
usually takes about 5 to 10 minutes for the pressure in a system, with
good valves, to equalize.
- During this time, the blower’s speed is smoothly dropping
towards the minimum speed. The coil is cool, the coil is draining, and
there is no re-evaporation.
SUMMARY
Temperature controlled blower speed:
-
Eliminates
the problem of blowing water off A/C coils.
-
Results
in maximum humidity removal by automatically adjusting for latent loads.
-
Allows
comfortable and quiet continuous blower operation that permits all
accessories attached to an HVAC system to operate at full-time at full
efficiency.
-
Increases
efficiency.
Learn about FanHandler products for...
[ Heating & A/C ] [ Zoned Systems ] [ Head Pressure ] [ Motors ]
|